DSC PC 1832 does not take entry delay time

Calemdq
Calemdq
23.097
hace 5 años
hace 5 años
I have an alarm center DSC 1832 in my workshop, and it turns out that I was able to terminate the contract with the monitoring company, but they completely deprogrammed it. Looking at other questions I could program it according to what I could understand. Of the 8 zones only 4 are used, zone 1 is for entry and exit and the rest are instantaneous, from 5 to 8 they are not used. I programmed this: * 8-5555-001-01-03-03-03-00-00-00-00 # Then the entry and exit delay times like this: * 8-5555-005-01-060-060-060 # And the siren time like this: * 8-5555-005-09-010 # In this way I understand that it should have 60 seconds to exit once activated, and 60 seconds to enter without activating the siren. And the siren that sounds 10 minutes What happens is that while I have the time to leave without sounding, when I enter the siren it fires instantly. I think I'm missing something, if someone can help me please I will thank you very much. Cheers !!
andresvazquez11
hace 5 años
hace 5 años
hello good morning, it is important to know which area is the one that sounds when you enter is the Z1? And the other zones are not in the entrance sector, so you do not comment, we would also have to verify if the programming is taking effect, to verify this you can put the exit time in 5 seconds and see if the change takes place as a test Important are the tests being performed by activating the alarm and entering as soon as the exit time ends or are the tests from one day to the next? if they are trying to activate and enter at the moment, in section 013 turn off the light 6, and comment as it was The programming steps you describe above are correct regards Andrew
Calemdq
Calemdq
23.097
hace 5 años

Hi Andres, thanks for your response, indeed the zone through which I enter is zone 1, the rest of the zones are instantaneous, to test I have put the time of entry and exit in 15 seconds, I do them all waiting for the end of the time, at this moment I am not in the workshop but later I will go, and I am sure that when you open the door you will shoot the siren instantly, because yesterday afternoon he did it repeatedly, only that I left it activated last night knowing that today it is going to ring to leave the workshop protected. I will try 013 and then comment, regards!

Responder
andresvazquez11
hace 5 años

when you arrive, comment if the siren sounds instantly to you, the 013 is only if all the tests are when you are active and deactivated at the moment, but if you leave it as you comment for a while or one day for another and it sounds when entering that no is.
Let me know and see what may be happening

Responder
Calemdq
Calemdq
23.097
hace 5 años

Andrés, I commented that this morning when opening the door of the workshop the siren shot instantly, I put the command you told me in section 013 I turned off the led 6 I tried again and the instant shot was repeated. For the doubts I noticed that zone 1 is the one that corresponds to the entrance door and is correct, apart I tell you that before rescising the monitoring, the alarm worked well, but the very turks deprogrammed it when I discharged the service, good people saw?

Responder
andresvazquez11
hace 5 años

Check you have led keyboard or lcd, and the area that is triggered you realize because it is warned on the keyboard or because you just open the door is triggered, after the shot doing * 3 you can see what area was shot to discard it is another shooting zone

Responder
Calemdq
Calemdq
23.097
hace 5 años

Andrés, today I am in the workshop, I did what you suggested in section 013 to turn off LED 6, I tried it later and now it works perfectly as it did before. I appreciate your help, greetings from Mar del Plata!

Responder
andresvazquez11
hace 5 años

I'm glad it was fixed, a hug!

Responder
Reparaciones similares solucionadas

¿Conoces una solución?

¡Aprende a reparar con estos cursos YoReparo!

4.87
(15)

Curso Diseño de Amplificadores de Máxima Fidelidad

Maximiliano Resch
$ 29 USD
$ 13 USD
4.71
(7)

Curso TV OLED y QLED con el Ing. Picerno

Ing. Alberto H. Picerno
$ 29 USD
$ 10 USD
4.64
(45)

Curso Tecnología Inverter - Fabricación de probadores y herramientas

Yamil Alarcón
$ 240 USD
$ 40 USD
¿Tienes una mejor respuesta a este tema? ¿Quieres hacerle una pregunta a nuestra comunidad y sus expertos?
Regístrate gratis