Good morning, I already changed the temperature sensor and it keeps blocking, change the condenser card, the pressures are 55 low and 200 high r22, greetings
For r22 the pressures are very low you should raise the suction around 65Psi, the high will go for 250 psi
Load at 65 psi and 250 at high, but the blockage continued, change the temperature and well sensors, working very well, it no longer locks, greetings