mongolia
hace 6 años
hace 6 años
I have to repair a 640 liter well freezer, with 404 refri and needing at least -18. to preserve ice cream The first thing I noticed was that I had little low pressure, 4 negative psi. and froze the return a little. the temperature in the upper part of the interior was adequate, but in the bottom it was lower, -9, and in the lower parts it did not frost. I add coolant, it starts to frost below and the entire return to the compressor is filled with ice. I leave the pressure at 15 psi, the next day down marks -18, and so for two days, the third marks -15 below. The client tells me that this temperature is not enough to keep ice cream. Will it be a half-clogged filter ?, and I would also like to know what to do if, when removing the filter, it is full of oil, thanks.
lusangor
lusangor
56.366
hace 6 años
hace 6 años
Hello Possibly what you say If you find oil in the filter, you have to start from scratch, good cleaning of the surgeon, empty ......... Regards
gabriel3299
hace 6 años
hace 6 años
Hello, if you should change the filter, but first estrogen and look for possible loss, if there is no leakage with 141b and nitrogen, change the filter load gas and voila, comments! regards!!
mongolia
hace 6 años

The filter did not have any oil, if it was quite covered, and also the condenser had a lot of fluff with dust stuck between the cells, which hindered the circulation of air. Thank you all for your opinions.

Responder
Fermin 007
Fermin 007
57.307
hace 6 años
hace 6 años
If you find oil in the filter, maybe the compressor already spits a lot of oil and you have to cheat it, regards
Romer
Romer
295
hace 6 años
hace 6 años
You will surely find oil in the filter. That is because he worked with low vacuum pressure. The R-404a when there is a leak is not recommended to increase, you have to discard the remaining gas and charge it again. This is because it is not a pure gas, it is mixture. As colleagues tell you, change the filter, clean the system with nitrogen and charge gas again. Of course you must find the leak first.
Reparaciones similares solucionadas

¿Conoces una solución?

¡Aprende a reparar con estos cursos YoReparo!

4.93
(14)

Curso Reparación de Equipos de Audio de Alta Fidelidad

Maximiliano Resch
$ 60 USD
$ 20 USD
4.84
(25)

Curso Práctico de Reparación y Bobinado de Motores Eléctricos

Héctor Castiñeira
$ 60 USD
$ 20 USD
4.64
(11)

Curso Electrónica para Reparación de Placas

Santiago Cediel
$ 29 USD
$ 11 USD
¿Tienes una mejor respuesta a este tema? ¿Quieres hacerle una pregunta a nuestra comunidad y sus expertos?
Regístrate gratis