Capillary tube

Hernan Barrios
hace 6 años
hace 6 años
Hello, I went to repair a display refrigerator that had the capped capillary tube 0.08 mm for 3.15 meters, I did not get the same capillary and put a 0.07 mm for 3.25 meters, after 30 minutes of empty I proceed to pour the 134a refrigerant and start to freeze part of the condenser and the entire molecular filter, which could be the fault. From already thank you very much
gaston predazzi
hace 6 años

Beyond the capillary change, did you clean the circuit separately with 141b?

Responder
Hernan Barrios
hace 6 años

Hi Gaston, if you clean the device separately.

Responder
davidefrainrod
hace 6 años
hace 6 años
Hi, hernan usually when this kind of capillary plugging happens, you have to clean the whole bone equipment completely and change the filter. For what you say you have an obstruction, look at the new capillary or the new welds that you did, check it well and pay attention to this: It could be that you have an obstruction in the condenser and this is causing capillary effect, the capping restricts the refrigerant and lets pass very little then evaporates there greetings
davidefrainrod
hace 6 años

Shorten the capillary as the cold colleague says

Responder
friovega63
friovega63
11.849
hace 6 años
hace 6 años
Hi Hernán, obviously you have an expansion in the condenser, for having an obstruction in the condenser itself, generally when this happens the problem is located approximately an inch before where the freezing begins, the welding may have penetrated too much or the condenser was already covered before the work you have done. Perhaps he thought that everything was in the filter and the capillary, and in fact it was the dense or clogged condenser. The capillary should take into account that, being thinner in its inner diameter, it should have a slightly shorter length, and you on the contrary lengthened it more. I recommend leaving it in only 3 meters maximum. Luck. S @ lu2 friovega63.
Hernan Barrios
hace 6 años

Can I also know that it is an extrangulated pipe? The condenser suction pipe was a bit battered

Responder
Hernan Barrios
hace 6 años

Before welding the new capillary, I cleaned the evaporator and condenser separately!

Responder
Romer
Romer
295
hace 6 años

Hi, I think that filter is locked.
And I agree with colleagues that the capillary is very long

Responder
Hernan Barrios
hace 6 años

thank you very much everyone tomorrow I will make your respective changes
and I will give the results-

Responder
Reparaciones similares solucionadas

¿Conoces una solución?

¡Aprende a reparar con estos cursos YoReparo!

4.93
(14)

Curso Reparación de Equipos de Audio de Alta Fidelidad

Maximiliano Resch
$ 60 USD
$ 20 USD
4.73
(22)

Curso Reparación de Fuentes Conmutadas de PC y Equipos Electrónicos

Maximiliano Resch
$ 40 USD
$ 20 USD
4.6
(10)

Curso Localización de Fallas en Refrigeración en Heladeras/Neveras On/Off

Yamil Alarcón
$ 29 USD
$ 12 USD
¿Tienes una mejor respuesta a este tema? ¿Quieres hacerle una pregunta a nuestra comunidad y sus expertos?
Regístrate gratis