problem with an A / A spliss of 14 thousand btu

Rafael Rodriguezelectroni
hace 6 años
hace 6 años
cordial greetings I have a problem with a 14,000 btu splis the equipment does not cool enough I measure the pressure and this does not reach 70psi that is the normal of the equipment this is maintained in 100psi and this uses gas R22 I do not know if it is that it does not complime it necessary to lower the pressure to 70psi
Discortez
hace 6 años
hace 6 años
It seems that this equipment has already been repaired and passed gas, check the amperage of consumption of the compressor that is not above the working amperage that says the label of the equipment, if it is above is that gas past. Also this fault is given by failure in the revolutions of the turbine of the evaporator, you have to verify if the bearings are well. You also have to check that the evaporator coil is not dirty and plugged. I hope you get these proposals.
MAYNOR DE LEON2015
hace 6 años

I have happened in systems of refirgeracion that when low the compressor is already being damaged, greetings.

Responder

¿Conoces una solución?

¡Aprende a reparar con estos cursos YoReparo!

4.25
(8)

Reparación de Placa Main TV LED con el Ing. Picerno

Ing. Alberto H. Picerno
$ 40 USD
$ 20 USD
4.6
(10)

Curso Localización de Fallas en Refrigeración en Heladeras/Neveras On/Off

Yamil Alarcón
$ 29 USD
$ 12 USD
4.87
(15)

Curso Diseño de Amplificadores de Máxima Fidelidad

Maximiliano Resch
$ 29 USD
$ 13 USD
¿Tienes una mejor respuesta a este tema? ¿Quieres hacerle una pregunta a nuestra comunidad y sus expertos?
Regístrate gratis