Hello SEBAITU, I will upload an edited image, to my proposal of solutions, with the connection of its electrical diagram coupled to the universal electronic board, I do not know, whether or not the speeds coincide with each color, because the universal board, does indicate that speed , corresponds to each relay, but the original CONQUEROR diagram, does not detail the speeds by color, bone that is not known if the red wire for example, really corresponds to the lowest fan speed, the blue with the average and the black wire with the highest. Change them if necessary. S @ lu2.
The relay of the universal plate that indicates with the lines in red and blue, are not connected to anything, your team only has a common fan, so you do not need the Out Fan relay and it does not have a 4-way reversing valve because it is only to condition cold air, so you don't need the VR relay, which is connected to a repeat inverter valve, which is needed in other cold / heat models. S @ lu2.
Hello! First of all thanks for your explanation.
I tell you to connect everything as you indicate and can not start. Although it is noted that it makes a kind of effort to start every few minutes (noise of wanting to start) after a few seconds it is cut off and the compressor never starts. Idea what can it be? Thank you
Directly check the compressor, it could have some false contact in the input wires in its terminals, or broken cable. 2- (the fan should work, or not ?, because in that case the fan should also be checked by measuring that all its cables have communication between all, use the multimeter on the scale of 2 kilo ohm. 3- (check the capacitors with a capacimeter, as this could be damaged 4- (otherwise I should rethink a review for damage to the universal board. Comment if you doubt how to do the checks and I tell you. S @ lu2