But if the compressor and all components were measured before yesterday and everything works as it should without problems, the problem is when it starts to rain and the outdoor unit stops and remains stopped until the rain passes and after a few minutes of the rain it has stopped there it starts again the normal unit and cools 100% and produces good heat in the heat mode
The compressor is electrically isolated all its parts if you have a fault only when it rains is because the water is entering the condenser itself, generating a leakage of voltage which the plate detects and cuts its operation, there is no sensor that detects carries in a condenser to cut normal operation. If you have a texter, measure the three goods of the compressor with mass (the body of the compressor), the same goes for the fan cables, if any of the two gives you continuity, you will have to replace the part.
Continuity does not give neither the compressor nor the fan, the equipment is well armed and sealed
The interconnection cables are not indented? Check that is the only thing that can generate the fault if you already checked everything else. But check the installation of the house that did not lower the trend when it rains.
Hello, In the end we had to change the outdoor unit and the new outdoor unit works excellent in all climates, grax equal pa