Minisplit is repressed and compressor sr protects ...

Fran ortega
hace 5 años
hace 5 años
: | good afternoon, I check a 9000 BTU 220v Frigidaire minisplit, plate amperage is 3.5 amp and 5.5 amp maximum, which turns on normally, lowers its static pressure from 120 psi to 20 psi, freezes high line and subsequently defrosts and increases its pressure, until here everything normal. Subsequently, it continues to increase the amperage of the compressor and up to 7.9 amp and protects the working pressure up to 95 psi at the same time that the amperage is also increasing, which is what it reached before the compressor was protected ... he commented that approximately 2.5 months ago I had done maintenance on the equipment and gradually stopped cooling well, the client told me ... I don't know that the repression may be causing since the lines are fine. regards
TRIATLON99
TRIATLON99
6.267
hace 5 años

Hi, start by checking compressor capacitors and external forger.
Line tension.

Responder
Fran ortega
hace 5 años

Hello, thanks for the recommendation, I already did it and I changed the fan was devalued almost to half its value (1.2 of 2 uf), I am struggling with the lines I will also change them .. I would mainly be affected by repression in the system by the damaged capacitor ?, that is; I work for approximately 3 to 5 minutes

Responder
TRIATLON99
TRIATLON99
6.267
hace 5 años

If of course, the consumption and the working pressure are raised, tido depends on how diminished it is.
Change the compressor too.

Responder
Fran ortega
hace 5 años

It was made change of lines and change of capacitor, it worked perfectly and was left with working pressure of 65 psi and 3.3 amp. Excellent suggestion, thanks triatlon99 ..

Responder
omorma
omorma
15.708
hace 5 años

The solution is for triatlon99 ask him to formulate the answer as such and the point is for him not for me

Responder
omorma
omorma
15.708
hace 5 años
hace 5 años
Hi how are you, clean the condenser and take out some refrigerant leave it between 65 to 70 psi greetings.
Reparaciones similares solucionadas

¿Conoces una solución?

¡Aprende a reparar con estos cursos YoReparo!

4.84
(25)

Curso Práctico de Reparación y Bobinado de Motores Eléctricos

Héctor Castiñeira
$ 60 USD
$ 20 USD
4.6
(10)

Curso Localización de Fallas en Refrigeración en Heladeras/Neveras On/Off

Yamil Alarcón
$ 29 USD
$ 12 USD
4.64
(11)

Curso Electrónica para Reparación de Placas

Santiago Cediel
$ 29 USD
$ 11 USD
¿Tienes una mejor respuesta a este tema? ¿Quieres hacerle una pregunta a nuestra comunidad y sus expertos?
Regístrate gratis