My air does not cool.

Gustavo Hoyo
hace 5 años
hace 5 años
hello I have a cold air heat bgh silen air mod bse30ch of 3000 cal / h power 61270w and understanding of 6.1 amp. with refrigerant r22. the intale ise the vacuum is more than two meters away each unit. I measured the low price and it marked me 30 and did not cool. I add more gas until I reach 60 pounds as the seller recommends and I begin to cool but little. about 18 degrees at the exit of the evaporator unit. being at its maximum power. and note that the low-pressure tube (which is 1/2 inch was all frozen in its path until it reaches the coupling with the evaporator unit. Someone knows what the problem is that I have and what the solution would be since a thousand thanks
Gustavo Hoyo
hace 5 años

just in case I bought it used. I will have about 7 years the team but I bought it working well I saw it walking

Responder
Ricardo Ab.
Ricardo Ab.
5.181
hace 5 años
hace 5 años
Hello, I would give the impression that you have a restriction on the evaporator. Can the pipe have been crushed when folded? regards
Gustavo Hoyo
hace 5 años

HAAA CAN BE SOMETHING THAT WOULD HAVE TO DISASSEMBLE IT AGAIN

Responder
Gustavo Hoyo
hace 5 años

It was just that the low spout had been strangled when leaving the evaporator since milll thanks

Responder
diegote7937
hace 5 años
hace 5 años
Good, you should leave it running for a while and look at what pressure is established, since you can get to have excess fluid, and being an old equipment, they sometimes take time to achieve the desired compression. What the colleague says is also correct, I clarify it so that you do not disassemble anything before trying that
emma ojeda 26
hace 5 años
hace 5 años
I add in addition to what the colleagues who review filters and tangential say since an excess of dirt produces the same problem
Gustavo Hoyo
hace 5 años
hace 5 años
Thanks to all who answered my question I tell you that I had the strangled low spout at the outlet of the evaporated from already milll thanks to all problem solved
Reparaciones similares solucionadas

¿Conoces una solución?

¡Aprende a reparar con estos cursos YoReparo!

4.84
(25)

Curso Práctico de Reparación y Bobinado de Motores Eléctricos

Héctor Castiñeira
$ 60 USD
$ 20 USD
4.87
(15)

Curso Diseño de Amplificadores de Máxima Fidelidad

Maximiliano Resch
$ 29 USD
$ 13 USD
4.64
(11)

Curso Electrónica para Reparación de Placas

Santiago Cediel
$ 29 USD
$ 11 USD
¿Tienes una mejor respuesta a este tema? ¿Quieres hacerle una pregunta a nuestra comunidad y sus expertos?
Regístrate gratis