I already did that test feed the terminals directly and the team tries to start and acts the thermal protector of the compressor. When you try to start the consumption it goes to 25A. I also measured the terminals between common / common start / run, then measured the sum of the start / run coils and the values are wrong. I also measured continuity between the common and compressor housing and gives value. Therefore, clarify that the motor compressor must be replaced. My question is if the board has to send the 220V if or if it can happen that sends less voltage. If not, I also have to replace the plate?
The compressor is definitely damaged. What you need to know now is if the voltage drop was before the compressor was damaged since it could be damaged by receiving 160 V or if the compressor is the one that generates that drop. The point is not to put a new compressor and encounter another problem.