Hi Dr. Electron, there is no pipe freezing ...
I have thought that a pipe could be strangled, but I have taken special care when laying it. The pipe has a total length of almost 12 meters, the evaporator unit is practically the same as the evaporator unit.
Thank you!
From what you say the circuit of pipes is fine. It only remains to test by disconnecting the temperature sensor and also verify that it is not in direct contact with the evaporator.
The other would be that the compressor is damaged. And it makes me have wear on the engine's internal bushings which may explain the sudden stop when it reaches 60 psi. Many cases have come out like this and I confirm it because then I do the autopsy on the motorcycle compressors.
It may also be due to lack of oil if the gas was allowed to escape at the time of uninstallation.