Air conditioner

Freezing problem of coarse spout and evaporated serpentine

Oscar Aguirre4
hace 5 años
hace 5 años
Hello good morning I am fixing an air conditioner of 3000 refrigerators with R22 gas that had the burned fan motor change I installed I put the 3 meters of pipes as appropriate when I understand it, it marks me gas pressure 55 to 60 psi the amper 5.5 but I began to freeze the thick pipe and the evaporator serpentine my query is that it may cause me that is what I have to review
DANY
DANY
362
hace 5 años
hace 5 años
HELLO, IF THE LOW PIPE IS FREEZED IT IS XQ IS RETURNING GAS IN A LIQUID STATE AND NOT GASEOUS AS SHOULD BE TO THE COMPRESSOR, THE FORCER THAT CHANGED IS SHOOTING OR BLOWING OUT AIR HOW SHOULD I BE? OR IS THE FORCER WHO CHANGED IN THE RIGHT SENSE?
Oscar Aguirre4
hace 5 años

Hello, how are you? I looked at the fan motor, I did not get new and I sent it to wind and if it turns for the felt that it is wonderful but I do not know if at the speed that it would have to be I kept thinking about that and another one that the evaporator the forger is throwing a 1 degree below zero but when I installed it I was doing fine after two days I started to fuck

Responder
DANY
DANY
362
hace 5 años

HELLO EVERYTHING WELL, BUT YOU ADDED REFRIGERANT AND THE FORCATOR IS GETTING HEAT TO THE CONDENSER IT IS VERY LIKELY THAT THE POWER OF THE FORCATOR IS VERY DECREASED, TO MY HAPPEN I SOMETHING LIKE TO YOURS BUT WITH THE FORCER OF THE CONDENSER OF A CAMERA, I BURNED THERE WAS NO SPARE PARTS AND I HAD TO SEND BOVINAR, AND TO REMOVE THE CUSTOMER'S PURCHASE I PUT A FORCATOR OF LOW POWER AND HAPPENED THE RETURN, WHEN PUTTING THE BOVED ENGINE AGAIN, DID DO IT, MAYBE THIS BAD AND THAT IS THE PROBLEM.

Responder
omorma
omorma
15.708
hace 5 años
hace 5 años
Hello how are you, although the pressure would be correct but it cannot be cooling to -1 ° the evaporator, it must be between 2 ° to 4 ° take out a little refrigerant and see that this evaporator is well cleaned greetings.
Oscar Aguirre4
hace 5 años

If I already cleaned the evaporator before installing it again, everything is clean, that's why I don't know what else to do it is already driving me crazy this air fix one thing and jump another

Responder
lenin_jesus
lenin_jesus
5.034
hace 5 años
hace 5 años
Hello how are you doing? check if the evaporator is clean if it is dirty, it will lower your temperature and therefore the pipe goes down and the evaporator freezes give good maintenance greetings and comment on how you are doing
Oscar Aguirre4
hace 5 años

Thank you if I'm going to take that fan motor out again and I'm going to take it to see again why I play that the problem is that a downturn

Responder
Reparaciones similares solucionadas

¿Conoces una solución?

¡Aprende a reparar con estos cursos YoReparo!

4.93
(14)

Curso Reparación de Equipos de Audio de Alta Fidelidad

Maximiliano Resch
$ 60 USD
$ 20 USD
4.6
(10)

Curso Localización de Fallas en Refrigeración en Heladeras/Neveras On/Off

Yamil Alarcón
$ 29 USD
$ 12 USD
4.87
(15)

Curso Diseño de Amplificadores de Máxima Fidelidad

Maximiliano Resch
$ 29 USD
$ 13 USD
¿Tienes una mejor respuesta a este tema? ¿Quieres hacerle una pregunta a nuestra comunidad y sus expertos?
Regístrate gratis