Hello, thank you for answering my question and I apologize why I was wrong to ask in the interior terminal I have
TN 1L. 2L. 3L. And abroad I have
1. 2 (n). SLN IF I CONNECT FOLLOWING YOUR COUNCIL I AM FREE IN THE OUTDOOR UNIT EL BORNE (L). What dev do? And again thanks.
Yamodify the question and attach photos of the terminals the black is that of the outdoor unit
Hi Vicente: I uploaded the diagrams so with that we see the internal plans of the equipment and deduct the connections, personally I do not remember or have my own terminal record with that type of numbering, but we can deduce it.
You don't have the electrical diagram of the capacitor? One thing I do not know if I ask you, is if it is cold heat, because the evaporator terminal seems to be cold but that of the condenser, is apparently bridged to work with an evaporator unit only cold.
Well you can try the following connection. N with N2; L1 with 1; L2 with S; L3 with L, It would be best if you try all this without mounting the equipment and so you can modify the connections. By the bridges that the condenser has it seems that it is like to operate with a cold evaporator alone.
I connected it following your instructions and nothing happens what is strange to me is that even the display does not turn on does not give me an error code nothing I do not know what to do
Another thing that xescubri is even in the inner terminal sn the terminal N and in the ground terminal I have voltage ...
First determine what each terminal on the capacitor is, 1 and 2N would have to start only the MC, and S and L would have to activate the forcer and the 4-way valve.
To terminals 2n and 1 I gave 220 directly and nothing happened ...
I do not know if it would be correct to ask you this but if we could communicate by watsapp or call it would be great and I explain why I do not call a technician the issue is that I just put my own trade and the truth is that I do not have money to call yn technician to buy the air tybe that sell some things but they did not enable me to trade
Well, leave a fixed cable to the terminal that says 2N and with the other cable look for the different components of the capacitor, (YOU CANNOT TEST ON THE TERMINAL N BECAUSE IT IS THE ONE WHO HAS A BRIDGE WITH 2N
In the past there was a private contact, at present we cannot do it that way. I don't think it's very good to place our phones publicly.
Hi, I started the internal unit with the forced start button but the condenser does nothing to remove the cover of the plate and the fuse is fine, the plate lights a LED I suppose it is normal to press the contact directly and the compressor starts the evaporator when using Forced start-up turned on the display but does it happen that the control is out of frequency or that the receiver does not work properly?
If you work with a contact on the capacitor, you have to see the connection better, because you have to see which cable feeds the transformer. which is what activates the entire system in the condenser. Verify that data
I forgive my ignorance but I would like to know which cable is the one that commands the transformer?
Well, something that takes work but is very useful for you, take out all the caps of the condensing unit, that everything is in sight, (make sure that each screw is in the same place where it came from the factory). When you have everything uncovered you have to follow the wires. One phase and one neutral have to reach the transformer (220V) and the transformer comes out of two wires, one positive and the other negative that feed the contact which is commanded by a relay that may be on the evaporator board and other equipment They bring in the condenser.
Something I forgot to ask. Where does the equipment feed from? common cable and an outlet from the evaporator? Because if not, the connection is different.
In the indoor unit it has a 220 outlet and another 220 line arrives outside the terminal block