Air conditioner

15000fr equipment ,. pipe freezes

elositofrio
hace 5 años
hace 5 años
I went to clean this equipment and they tell me that it does not cool, it is a 15000 fr equipment. that works with a fancoil as an evaporator unit. When I speak the Evaporator, I see the serpentine totally frozen. The condenser with the drain pipe completely frozen, with refrigerant pressure R22 at 10 pci. I try to load gas and I can't overcome that pressure, as it doesn't let me. What I did was close the discharge line so I can load faster, but it is impossible. There will be a problem or is there a technique for loading. Thank you.
DANY
DANY
362
hace 5 años
hace 5 años
HELLO, GAS IS RETURNING THE COMPRESSOR IN LIQUID CONDITION THAT YOU HAVE FROZEN THE LOW LINE, BEFORE LOADING GAS, I ADVISE YOU TO CLEAN THE CONDENSER, IF YOU HAVE A BETTER WASHER, BUT START TO TAKE A BALD OF AGAIN WITH CLEAN WATER, AFTER THAT TEST THE PRESSURE AND AMPERAGE EQUIPMENT, VERIFY THAT THE LOW LINE DOES NOT FREEZE, IF YOU PERSISTS THE PROBLEM IT IS LIKELY THAT THERE IS A PARTIAL OBSTRUCTION OF THE PIPE, THE FILTER MAY BE VERY COVERED. TEST THE CLEANING FIRST TO GO DISCARDING.
elositofrio
hace 5 años
hace 5 años
solved Thanks a lot.-
Reparaciones similares solucionadas

¿Conoces una solución?

¡Aprende a reparar con estos cursos YoReparo!

4.84
(25)

Curso Práctico de Reparación y Bobinado de Motores Eléctricos

Héctor Castiñeira
$ 60 USD
$ 20 USD
4.87
(15)

Curso Diseño de Amplificadores de Máxima Fidelidad

Maximiliano Resch
$ 29 USD
$ 13 USD
4.64
(11)

Curso Electrónica para Reparación de Placas

Santiago Cediel
$ 29 USD
$ 11 USD
¿Tienes una mejor respuesta a este tema? ¿Quieres hacerle una pregunta a nuestra comunidad y sus expertos?
Regístrate gratis