Hello that brand has a 5k sensor, if you changed to one of the same characteristics and the failure continues, you have problems in the memory of platelets (usually happens in that brand)
You can place a new or universal.
regards
I thought about that ... because when measuring it in 20 K with the tester ... it gives me something of 4.58 but both two ,,,, the new and the old ... I think there will be no other solution than to buy a platelet new ..... thanks !!
this sensor is double ... that is, if or if you have to change the environment with the well ... I measured the sensors in 20 K and it gives me something of 4.58 ... both two ... the new one and the old....
if both sensors measured them and they are good then you have problems with the electronic board