Air conditioner

LG 110 small air conditioner

Luislugo
hace 5 años
hace 5 años
I have a problem with the compressor of a window air conditioner LG 110. The fault is in the compressor. Specifically in the current terminal that is placed in the compressor. In the compressor there are 3 wires that each carry their terminal but the three that always carry electricity are burned. This terminal is flag shaped. I have placed it 3 times but it lasts 2 days and then burns. I tried a new one, turned it on and left it on for a minute and then turned it off and when it touched the terminal it was very hot. Is it normal for it to get so hot? And the other is that when I have put this terminal on electricity, sometimes it has sparkled when I have turned it on and I had to turn it off quickly. And then I re-tighten the cable well and stop making a spark and start normal but it warms up a lot if I continue like this every two days I will be changing terminals. What would be the problem? Regards
Castelar
Castelar
222
hace 5 años

The three terminals carry electricity to the motor. The female terminal is called Faston flag and when it is placed it must be tight (on its own, you should not use a tool to tighten it, if to crimp it to the cable).

Responder
Mimol92
Mimol92
8.033
hace 5 años
hace 5 años
Good evening, you must check the compressor's electrical consumption, it must be too high to damage every 2 days said terminal, which is probably the common one (C), if the consumption is too high, the state of the motor coils should be checked , it is likely that it is grounded (grounded), or that some coil is overheated, in which case the compressor would have to be replaced, there are also cases in which the compressor has mechanical problems, it can last a few days working well and suddenly it paste the mechanism, it happens very little but it has happened, they are compressors that are in a state of intermittency (sometimes they work well but suddenly they stick together), and when it sticks it lifts the electricity consumption and if the electrical terminal is not of good quality, it will end bursting, I also suggest you check that the rear honeycomb is not too covered with dirty, that is another cause for raising power consumption, and if you live in Venezuela, it is common for this to happen if you do not have With voltage protectors in the face of the constant electrical fluctuations that occur in the country, at each fluctuation (downturn) the compressor turns off and on again in less than a second, coupled with the fact that in each downturn the 110 rises to 140 and 145 volts, the motor will raise its electrical consumption and could end up bursting the terminal if the thermal protector does not act in time.
Reparaciones similares solucionadas

¿Conoces una solución?

¡Aprende a reparar con estos cursos YoReparo!

4.84
(25)

Curso Práctico de Reparación y Bobinado de Motores Eléctricos

Héctor Castiñeira
$ 60 USD
$ 20 USD
4.6
(10)

Curso Localización de Fallas en Refrigeración en Heladeras/Neveras On/Off

Yamil Alarcón
$ 29 USD
$ 12 USD
4.71
(7)

Curso TV OLED y QLED con el Ing. Picerno

Ing. Alberto H. Picerno
$ 29 USD
$ 10 USD
¿Tienes una mejor respuesta a este tema? ¿Quieres hacerle una pregunta a nuestra comunidad y sus expertos?
Regístrate gratis