It is very important to try if you have the equipment to test with nitrogen, in particular I leave it at least from one day to another and if it does not lower the needle I proceed to the rest that guarantees a good job as well as saving time and money, it is only an opinion!
Here nitrogen is very expensive. We use 300 psi air and soapy water to detect leaks. Then a good vacuum. And ready gas was charged. After finishing, I turn off the unit and with the same equilibrium pressure it is verified that there is no leakage with soapy water.
The forcers work normal. The idea of consumption is good. Assuming that I have a high consumption problem should be obstruction. And if the consumption is low it must be leak. I will do that, thanks apiconaut.
Hello friend, I already solved, indeed the consumption was low, in the case of a split air of 12000btu / h and 220 volts, the normal consumption is 5.7 A according to the plate. And in the measurement it gave me 2 A. So I looked for the leak and found it at the high junction. Thank you.