Cold-heat air, 3800fg, does not raise pressure.

Anibal_el_tecnico
hace 5 años
hace 5 años
Hello, good afternoon, I am starting on the subject and with little experience, install a cold heat, I made it empty and it does not announce a loss with a pressure gauge, I proceed to break the vacuum with r22, the needle rises momentarily and returns to its empty position, The compressor overheats and the consumption does not rise by 3A. Test the reversing valve and it is correct, the question would be ... Do I proceed to disassemble the equipment to find any possible obstruction or is there any other test that I have left to do?
DANY
DANY
362
hace 5 años
hace 5 años
HELLO ANIBAL, FIX THAT THE TWO VALVES (HIGH AND LOW) ARE WELL OPEN THE LOW PRESSURE PRESSURE MUST BE AT 125 130 PSI, WHEN TURNING THE EQUIPMENT IN COLD MODE THE PRESSURE HAS TO LOWER AND RAISE UNTIL STABILIZE BETWEEN 62 AND 65 PSI, IF THE PRESSURE IS GOING TO ZERO PSI OR EMPTY IS XQ IT DOES NOT GAS, I OPENED A LITTLE KEY OF THE MANIFOLD TO SEE IF GAS COMES OUT, FOR ME IT DOES NOT GAS X WHAT YOU SAY.
Anibal_el_tecnico
hace 5 años

The two valves open completely the pressure is kept below zero, corresponding to the vacuum, adding the refrigerant the vacuum does not break, when the equipment is turned on either, the equipment does not have gas, so the load that tries to carry it out. The evaporator does not change from room temperature, when adding a small jet of gas of about 5 seconds it is possible to cool the high pipe, so it occurs to me that an obstruction does not allow the gas to complete the circuit.

Responder
DANY
DANY
362
hace 5 años

OK, I BELIEVE THAT I UNDERSTANDED YOU, I EXPLAIN HOW I LOAD IT WHAT I WAS TAUGHT AT SCHOOL (R22), TURN ON THE EQUIPMENT IN COLD MODE ONE TIMES IN OPERATION, OPEN THE GARRAFA AND LEAVE GAS FOR A MINUTE WITHOUT MISSING THE 60 PSI WHILE GAS IS ENTERING, CLOSE THE GARRAFA, THE PRESSURE WILL LOWER LEAVES A SECONDS TO BE STABILIZED TO REPETIS HOW MANY TIMES IT WILL BE NEEDED UNTIL REACHING A WORK PRESSURE BETWEEN 62 AND 65 PSI, YOU WILL KNOW THAT IT FREEZES COMPLETE THE HIGH PIPE IS NORMAL THAT, ONE ONCE THAT BEGINS TO FILL HIMSELF ONLY, GIVE IT WITH CONFIDENCE. HEALTH

Responder
DANY
DANY
362
hace 5 años

I FORGOT SOMETHING, IF THE TEMPERATURE IS XENCIMA OF THE 26 C YOU'LL HAVE A NORMAL PRESSURE BETWEEN 62 AND 65 PSI, IF IT IS BELOW THE 25 24C IT WILL NOT RISE BEYOND THE 50 OR 55 PSI

Responder
omorma
omorma
15.708
hace 5 años
hace 5 años
Hello how are you, if you checked with nitrogen that does not leak, perform empty load by weight according to the indication of plate until it does not come into operation until the load is completed controlling pressure and amperage, if after this load the pressure is maintained in Vacuum is because there is a clogged filter or capillary or some crushed pipe, greetings.
Reparaciones similares solucionadas

¿Conoces una solución?

¡Aprende a reparar con estos cursos YoReparo!

4.84
(25)

Curso Práctico de Reparación y Bobinado de Motores Eléctricos

Héctor Castiñeira
$ 60 USD
$ 20 USD
4.87
(15)

Curso Diseño de Amplificadores de Máxima Fidelidad

Maximiliano Resch
$ 29 USD
$ 13 USD
4.64
(11)

Curso Electrónica para Reparación de Placas

Santiago Cediel
$ 29 USD
$ 11 USD
¿Tienes una mejor respuesta a este tema? ¿Quieres hacerle una pregunta a nuestra comunidad y sus expertos?
Regístrate gratis