Hi there are teams that the reversing valve in cold mode are enriched, they are normal in heat mode.
With respect to the platelet I have not changed in floor-to-ceiling equipment, but I saw universal placed.
Consult an important refrigeration house they know or expect that a colleague will help you.
regards
Hello Dok, as it goes, the ideal is to repair the original, but there is no option, the plate that is normally used for such equipment is a universal plate of A. Acond. Ceiling floor, model Qd-u10a, googleala, you get about 1 luca. I have to comment you some details regarding the flapers swing. What I am still thinking about is the subject of the valve, this plate will energize the valve in heat mode, the opposite of how you need it.
Once, reading a forum, he said that the air conditioners f / c that have the inverting valves that are energized in cold mode and rest in heat mode, it was because those equipment were intended for use in regions where the cold predominates, and they are used for heating and too little to cool ... if the valve burns, you don't run out of heating ... I don't know if it's true, it can be a matter of design too .... regards
Thank you very much dear colleagues. I begin to realize that my conclusions were right then about the reversing valve. I had never seen that. I have learned something new !! and regarding the board to use, then I will comment which one I install. Surely this will take me a couple more days, since where I have to install it is on site. triatlon99 I appreciate your contribution. SplitBoy, thanks too. the original platelet does not go, literally ate the rats where the equipment was stored. I am looking forward to your contributions on the flapers. I keep in touch thanks !!!!!
The theme of the flapers on that plate that the model passes you, is that it has a 5-pin comb at 12 v where it has a common at one end, and it depends on how you put it, it turns to one side or the other, when it turns off, You have to check that the deflector lid is closed, if it stays open, you have to turn the chip in the comb and that's it. The issue is, if you have 2 flapers, there is only one tab. I particularly use the plate in a BGH of 15 frig. And it has only one flap. you would have to attach them to a card and see if the deflector covers close parallel or meet, I don't know if I explain Dok.
Hello dears!! Today I was working on the team in question. In fact, as you said, it has a "Normal heat" cycle reversing valve. This is new for me. Well, I decided to install a universal plate, they are sold in the houses of the bouquet and they are called "for ceiling floor", like the equipment. They cost $ 1000. The inverter valve must be connected together with a "Normal closed" type contactor, so that when the heat order is given, the plate will de-energize the valve. As for the flapers, then I tell them. thank you very much !!!!