Thanks for the correction is certainly as you say .. today I try and then comment ... thank you very much
Hello, I tell you ... assemble the plate with the correct sensors and continue to throw me the same fault .. it starts a short time 3 or 4 minutes (we always talk about the heat mode) and the air starts to cool ... cut the equipment and the freezing light remains ... I checked the gas ... 110 pounds with a temp. exterior of 12 gds..and in cool mode it is perfect ... if anyone can know what it is I would appreciate if you doubt me ... thank you very much ..
R410 ... around noon with an acceptable room temperature was close to 120 lbs ... the issue is that cold performs very well ... and in heat ... well I already explained the fault and I can not find it ... last Would a universal plate be convenient and less cumbersome ...?
That pressure is for 30/35 degrees ambient.
I take the heat pressure those minutes that works?
When you cut everything goes out, or outside and inside ????
Comment
When it cuts, it turns on the fault light that is on the display ... this model only brings the ignition light and the fault light ... and cuts compressor..forcer and turbine..if I place the well sensor in a container hot .. starts .. and if I wait for 10 ..15 min it also starts but after 5 minutes the team stops ... let's say it is 5 for every 15 stopped .. and in the cold function it has no problems
Sorry ... it would not be the fault light (when the fault mark is flashing the light) ... it would be the freezing I estimate ... and I plant the equipment ..