Air conditioner

Split plate LG 4500 does not start in heat

Alejandro Lusich
hace 6 años
hace 6 años
I am working on a split cold equipment lg heat of 4500 eh..Change the sensors ... I placed 5 k and 10 k the spout ... I stopped the equipment as if it was frozen .. Learn the defrost light and it does not start anymore ... and if I heat the sensor with hot water it starts ... the sensors are in the indicated values ... any suggestions .. ???
TRIATLON99
TRIATLON99
6.267
hace 6 años
hace 6 años
Hi, you are doing a different temperature reading. Lg uses 10 k ambient and 5 k well sensor. Regards
Alejandro Lusich
hace 6 años

Thanks for the correction is certainly as you say .. today I try and then comment ... thank you very much

Responder
Alejandro Lusich
hace 6 años

Hello, I tell you ... assemble the plate with the correct sensors and continue to throw me the same fault .. it starts a short time 3 or 4 minutes (we always talk about the heat mode) and the air starts to cool ... cut the equipment and the freezing light remains ... I checked the gas ... 110 pounds with a temp. exterior of 12 gds..and in cool mode it is perfect ... if anyone can know what it is I would appreciate if you doubt me ... thank you very much ..

Responder
TRIATLON99
TRIATLON99
6.267
hace 6 años

Hello, what gas do you use?

Responder
Alejandro Lusich
hace 6 años

R410 ... around noon with an acceptable room temperature was close to 120 lbs ... the issue is that cold performs very well ... and in heat ... well I already explained the fault and I can not find it ... last Would a universal plate be convenient and less cumbersome ...?

Responder
TRIATLON99
TRIATLON99
6.267
hace 6 años

That pressure is for 30/35 degrees ambient.
I take the heat pressure those minutes that works?
When you cut everything goes out, or outside and inside ????
Comment

Responder
Alejandro Lusich
hace 6 años

When it cuts, it turns on the fault light that is on the display ... this model only brings the ignition light and the fault light ... and cuts compressor..forcer and turbine..if I place the well sensor in a container hot .. starts .. and if I wait for 10 ..15 min it also starts but after 5 minutes the team stops ... let's say it is 5 for every 15 stopped .. and in the cold function it has no problems

Responder
Alejandro Lusich
hace 6 años

Sorry ... it would not be the fault light (when the fault mark is flashing the light) ... it would be the freezing I estimate ... and I plant the equipment ..

Responder
omorma
omorma
15.708
hace 6 años
hace 6 años
Hello, how are you? If, when the sensor is heating, the inner turbine starts, it is missing refrigerant and when it does not reach the temperature it does not turn the turbine, it places the equipment in cold mode. then complete the load if it is R22 no problem if it is R410 you must have 60% to complete the load with inverted carafe and diffuser valve if you have less full load is made with balance greetings.
Reparaciones similares solucionadas

¿Conoces una solución?

¡Aprende a reparar con estos cursos YoReparo!

4.93
(14)

Curso Reparación de Equipos de Audio de Alta Fidelidad

Maximiliano Resch
$ 60 USD
$ 20 USD
4.6
(10)

Curso Localización de Fallas en Refrigeración en Heladeras/Neveras On/Off

Yamil Alarcón
$ 29 USD
$ 12 USD
4.87
(15)

Curso Diseño de Amplificadores de Máxima Fidelidad

Maximiliano Resch
$ 29 USD
$ 13 USD
¿Tienes una mejor respuesta a este tema? ¿Quieres hacerle una pregunta a nuestra comunidad y sus expertos?
Regístrate gratis