hace 6 años
= 10.0pt Good evening. = 10.0pt Looking forward to your suggestions. = 10.0ptI am repairing a DP mark air of 36,000 BTU, RLA current is 19.5 Amp., Which presents and / or observes the following:
[list=1]
[*] = 10.0pt Evaporator unit freezing, suction pipe (thick pipe) and reaches the base of the compressor.
[*] = 10.0pt The fine pipe remains warm to the touch.
[*] = 10.0pt The fine pipe dryer filter remains warm to the touch.
[*] = 10.0pt The condensing unit has no capillary. = 10.0pt
[/list]
= 10.0pt I have done the following activities:
[list=1]
[*] = 10.0pt Capacitor test. In the condensing unit, replaced the compressor (55 uF) and the fan (6uF). They measured 42 uF and 2.5 uF. The evaporator unit is good. [/B]
[*] [b] = 10.0pt Current and pressure measurement: 20.5 Amp. and 43 psi.
[*] = 10.0pt After performing steps a and b, I performed maintenance on the evaporator unit and then measured the current and pressure: 16.5 Amp (low consumption) and 43 psi (no pressure change).
[*] = 10.0pt After performing all of the above, I proceeded to introduce refrigerant to complete pressure. The current rose to 20 Amp. and the pressure was maintained at 43 psi. = 10.0pt
[/list]
= 10.0pt Question:
[list=1]
[*] = 10.0pt After maintenance, what is the reason why the current dropped and the pressure did not change?
[*] = 10.0pt When refrigerant was introduced, why did the current rise and the pressure was maintained?
[*] = 10.0pt Where is the expansion valve of this equipment located?
[*] = 10.0pt Is it possible that the valve is clogged and is the cause of the freezing?
[*] = 10.0pt Have I skipped any steps or procedures in the evaluation?
[/list]
= 10.0pt [/b[[b[=10.0pt[/b[[b[=10.0ptIappreciateyoursupport.
¿Realmente quieres cerrar esta reparación?
Sí
No
¿Realmente quieres reabrir esta reparación?
Sí
No
¿Realmente quieres borrar este post?
Sí
No