I did the vacuum when I installed it the first time 40 min. and then there will be the high and low keys when I realized that it does not cool connect the pressure gauge and it only marked me 10 psi I thought that it would only be necessary to tighten the nuts and bolver to load gas but I realized that it began to freeze the line of high forget to mention that it is 12000 btu and the pipes did not increase with which it brought alknso
Ok, if I understood
When you checked that it did not cool and was frozen, did you put your air in ventilation mode so that it defrosted or so frozen, did you check pressures? If so, you must wait for it to thaw and then check pressures. And if you checked pressures already defrosted the equipment and it gave you 10 psi you should have leak check the connections with soap maybe you squeezed too much and damaged the countersink