Air conditioner

Hitachi Model ra3000 fsn window air conditioner

Marcos Antonio Zarza
hace 6 años
hace 6 años
Measuring evaporator inlet and outlet I have 30 temperature, no freezing of any of the pipes is observed, neither high nor low I measured the capacitor that says it is 30 nf and it gives me 29 nf that would be the problem of xq not cooling completely and not cutting. The thermostat works well because I tried it
omorma
omorma
15.708
hace 6 años
hace 6 años
Hello how are you, the capacitor is well within the tolerance of + -5% the pipes may not freeze because you lost all the refrigerant due to a leak you should measure the pressure of the refrigerant and check that the equipment is well clean greetings.
Marcos Antonio Zarza
hace 6 años

Very well although I see that the force is lacking the force of the forcer

Responder
omorma
omorma
15.708
hace 6 años

It can be the motor or the capacitor

Responder
Reparaciones similares solucionadas

¿Conoces una solución?

¡Aprende a reparar con estos cursos YoReparo!

4.93
(14)

Curso Reparación de Equipos de Audio de Alta Fidelidad

Maximiliano Resch
$ 60 USD
$ 20 USD
4.6
(10)

Curso Localización de Fallas en Refrigeración en Heladeras/Neveras On/Off

Yamil Alarcón
$ 29 USD
$ 12 USD
4.87
(15)

Curso Diseño de Amplificadores de Máxima Fidelidad

Maximiliano Resch
$ 29 USD
$ 13 USD
¿Tienes una mejor respuesta a este tema? ¿Quieres hacerle una pregunta a nuestra comunidad y sus expertos?
Regístrate gratis