Air conditioner

Cold / heat split does not reach the room cold

Bryanezequiel16
hace 6 años
hace 6 años
Hello good morning forum ... I have a problem with a 3.2W COVENTRY cold / heat split ... which had no gas ... I had lost in the connection nuts ... I cut and welded ... that is solved ... then I pressed with 400 psi nitrogen ... and threw me lost in the reversing valve in 2 of its 3 pipes ... I welded them and pressurized again and never lost again ... I continued to empty the needle did not move .. I broke the void with r22 and started the team. the compressor started and automatically the low pressure stagnated 100 psi ... but the cold does not reach the evaporator ... my doubt would be that the valve could have been clogged ... I really lost my way I could not solve it ... I would appreciate some help
omorma
omorma
15.708
hace 6 años

Call a responsible and knowledgeable technician to repair what you destroyed

Responder
TRIATLON99
TRIATLON99
6.267
hace 6 años

Hi, you can release the coolant if there is little you loaded, loosen pipes and test the engine.

Responder
NG en linea
NG en linea
9.229
hace 6 años
hace 6 años
Even if there were problems in the inverter due to no gas flow or having sealed the gas flow in another area, the pressure should be empty, that compressor is not sucking. When you turn off the compressor, what pressure do you have?
Bryanezequiel16
hace 6 años

When I turn it off the low pressure goes to the limit ... and when I turn it on it goes back to 90 or 100 psi

Responder
Bryanezequiel16
hace 6 años

When it is switched on it is not going to be empty it remains stagnant in that pressure 90 psi

Responder
NG en linea
NG en linea
9.229
hace 6 años

Friend coordinates the answer to help you
1- compressor walking how many psi
2 compressor stopped how many psi
Only those two data

Responder
Bryanezequiel16
hace 6 años

Compressor walking 90 psi
Compressor stopped 250 psi

Responder
NG en linea
NG en linea
9.229
hace 6 años

If the gas used by your device is r22a, you are exceeded by gas. This refrigerant works with 65 psi in the suction and high between 230 to 250. Just as you are going to nail the compressor

Responder
Bryanezequiel16
hace 6 años

So what I have to do is take out gas ... and nothing else. At the time I solved the loss to the valve could be leaved

Responder
Bryanezequiel16
hace 6 años

By the time I welded the valve it could have broken inside. "Or the capillary that passes x below." It is the first time I have a job like this ... the compressor starts the fan too ... only the stopcocks cool and nothing more ... the valve raises a lot of temperature

Responder
NG en linea
NG en linea
9.229
hace 6 años

Put the manifold and see it slowly taking gas waiting for the system to stabilize until it reaches 65psi

Responder
Reparaciones similares solucionadas

¿Conoces una solución?

¡Aprende a reparar con estos cursos YoReparo!

4.84
(25)

Curso Práctico de Reparación y Bobinado de Motores Eléctricos

Héctor Castiñeira
$ 60 USD
$ 20 USD
4.25
(8)

Reparación de Placa Main TV LED con el Ing. Picerno

Ing. Alberto H. Picerno
$ 40 USD
$ 20 USD
4.87
(15)

Curso Diseño de Amplificadores de Máxima Fidelidad

Maximiliano Resch
$ 29 USD
$ 13 USD
¿Tienes una mejor respuesta a este tema? ¿Quieres hacerle una pregunta a nuestra comunidad y sus expertos?
Regístrate gratis