good morning all I have the following drawback: I called customer to see the air because it does not work: the sequence that does is the following:
I plug in and power up
indicates the power to the plate by means of the buzzer (a long beep is heard)
I put on cold and I expect
the MC relay is heard and the external FAN is turned on, not the internal FAN.
Disposal of ambient sensor.
I focus more on following the fault for the internal fan (turbine)
I check turbine engine: I turn it by hand, at first glance it is observed that it is in good condition. it has no dirt or grease.
I remove the plate by disconnecting all the pieces and I take it to the workshop
in workshop the alilmento with trafo 12V
connect sensors and the digital command panel
when energizing it sounds and gives the normal beep
I turn it on by remote control
re-mark the same error. this error gives it 3 seconds after it turns on the MC relay and external FAN. in the digital one puts E4 and cuts everything.
only does not do it when I put ventilation mode
control motor capacitor 1.5uF turbine and gives me 1.42uF to my understanding is fine and I discard it.
I understand that although I try the plate without connecting the motor of the fan inside should not give me the error, so the fault is in some component of the plate that does not allow to follow the sequence of ignition and cuts it.
for now I'm still looking for the fault.
the plate with the naked eye does not show any malfunction.