Overvoltage and low voltage protective installation ...

caramelino90
hace 5 años
hace 5 años
Hello people from the community of me I repair ... I need to install an over and under voltage protector, it is a "tele haase model e1ym400vs10 made in Austria dimmable" ... 1-how to connect each protector terminal? 2-what is it for and how to regulate each knob presented by the protector? In total there are 4 little dogs ... Thank you very much already....
Ennio Montenegro.
hace 5 años
hace 5 años
If you have the manual, you can analyze the above. Terminals N - L1 - L2 - L3 are the neutral and the 3 phases in their correct sequence. The first knob is the delay of the operation, when it detects values outside the settings. The second is maximum voltage Un is the nominal voltage. The third is minimal tension. The fourth is the mode of operation. It can work in several ways, each is the selection. The attached image shows the protection modes. - U is only low voltage protection - U + S is protection by min voltage plus phase sequence - W is protection for min and max voltage adjusted with knobs 2 and 3 - W + S is protection for min max plus phase sequence Google translation of the manual Translation manual.docx [13.63kb] The delay is after exceeding the adjusted max or lowering the adjusted min. When the voltage is recovered to the adjusted max value, it is immediately reconnected, the same if it has dropped and recovered to the min value. Tight. This is for stress transitions, so that it does not cut immediately at the start of an engine for example.
caramelino90
hace 5 años

Hi Ennio, I was just asking why the installation manual is in English ...
How should I connect terminal 16-15-18? They would be those at the bottom of the protector ....
From already thank you very much I wait for the answer and I give you the assessment .....

Responder
caramelino90
hace 5 años

Ennio other consultations, according to knob 2 and 3 which are the ones that regulate maximum and minimum the scale is in percentage, how would the regulation be?
What do you mean by the percentage?

Responder
Ennio Montenegro.
hace 5 años

Terminal 15 is the common one and 18 is the normal open. So when connecting the power supply within the set parameters, contact 15-18 will close. When one of the phases goes out of the parameters, the red LED of min or max will flash and after the set time, the contact will open, the red LED being fixed.

Responder
Ennio Montenegro.
hace 5 años

If you do not know how to adjust the minimum and maximum voltage, comment and perform the calculation.
You just have to indicate how much you want it to operate for max and min.

Responder
caramelino90
hace 5 años

Hello Ennio, thank you very much and very kind of you for sharing your knowledge with the faints and dedicating time, a big hug ...
I will use the protector for a three-phase motor if it is not very complicated I would like to learn how the calculation for the regulation of min. And max ....
Why is the regulation scale expressed in porsentage?
The time that is regulated with the first knob, is the time it will take to reconnect once you return to normal? .....

Responder
Ennio Montenegro.
hace 5 años

In the answer I attach a translation of the manual.
Regards

Responder
Ennio Montenegro.
hace 5 años

In the case of pot 2 of 80% of 230 = 184V and 130% of 230 = 299V.
For pot 3 it is 70% of 230 = 161V and for 120% of 230 = 276V.

Responder
caramelino90
hace 5 años

Hello Ennio, I have to thank you for the time you spent and answer the questions that I was not clear about, thanks to you I managed to clear the doubts ...
I send greetings and a big hug from Córdoba Argentina ...

Responder
Ennio Montenegro.
hace 5 años

When you leave it operational, you can comment and if you can put images, so that it serves those who may have the same doubts.
Regards

Responder
Reparaciones similares solucionadas

¿Conoces una solución?

¡Aprende a reparar con estos cursos YoReparo!

4.25
(8)

Reparación de Placa Main TV LED con el Ing. Picerno

Ing. Alberto H. Picerno
$ 40 USD
$ 20 USD
4.94
(16)

Curso Refrigeración Comercial Aplicado a Diagnóstico y Reparación

Ing. Georga Melgarejo
$ 40 USD
$ 13 USD
4.64
(45)

Curso Tecnología Inverter - Fabricación de probadores y herramientas

Yamil Alarcón
$ 240 USD
$ 40 USD
¿Tienes una mejor respuesta a este tema? ¿Quieres hacerle una pregunta a nuestra comunidad y sus expertos?
Regístrate gratis