BR 6000 power factor controller gives overvoltage alarm and does not work. In the measuring terminal it gives 435 v. How do I repair it and get back to work.
Hi Ihanquilleo. Check the Undervoltage or Undervoltage adjustment value (so you call pretense?) that you have configured. If I am not mistaken it should be established when the device measures the voltage above that adjustment value and you may have this voltage set to a value very much your work limit.
Regards!
Hi Ihanquilleo
Like the capacitor bank, the voltage rises, you must measure without the connected bank and with the connected bank.
You have to check the settings, since for example the power factor of the network is for example 0.95 and you have a setting of 1.0, the bank can be connected in its entirety, increasing the voltage with low inductive load connected.