Automation and control

LOGO 8 230RCE connection at 220 or 240 volts

rubenchez
hace 6 años
hace 6 años
I will currently work with LOGO model 8 230RCE from Siemens. when reading the manual it indicates to me that the phase is connected to L1 and in N it is connected to neutral or common as I understand indicating that in L1 the voltage or voltage can reach or reach 240 volts. My question is due to the fact that where the voltage is installed is a three-phase system and I have 2 phases of 120 volts each. Can I connect one phase in L1 and the other in N? this would not cause damage to the equipment
siste2016
siste2016
1.968
hace 6 años
hace 6 años
Hello Ruben, in principle you have no problem in connecting one phase in L1 and the other in N, although make sure they are 240v., If this voltage exceeds, the source of the Logo can be damaged. You could install a 1 or 0.500 AMP transformer, all depending on the load, with 240v primary input. and 200 or 220v. In the secondary, right here in the secondary terminals you can connect L1 and N of the Logo, this way you have guaranteed your power, you will never receive more than 220 or 225v.
Reparaciones similares solucionadas

¿Conoces una solución?

¡Aprende a reparar con estos cursos YoReparo!

4.93
(14)

Curso Reparación de Equipos de Audio de Alta Fidelidad

Maximiliano Resch
$ 60 USD
$ 20 USD
4.6
(10)

Curso Localización de Fallas en Refrigeración en Heladeras/Neveras On/Off

Yamil Alarcón
$ 29 USD
$ 12 USD
4.87
(15)

Curso Diseño de Amplificadores de Máxima Fidelidad

Maximiliano Resch
$ 29 USD
$ 13 USD
¿Tienes una mejor respuesta a este tema? ¿Quieres hacerle una pregunta a nuestra comunidad y sus expertos?
Regístrate gratis