Sanitary

Automatic float diagram with submersible pump

adrian0364
hace 6 años
hace 6 años
Good afternoon I need if anyone has a diagram of connection of automatic float to submersible pump that turns on automatic and manual if any has I will thank
servimat1
servimat1
138.835
hace 6 años
hace 6 años
Hi. Is the pump monophasic or three-phase? I leave a basic one that is suitable for both types of engine. Regards
adrian0364
hace 6 años

It's monophasic thanks for the diagram

Responder
adrian0364
hace 6 años

Greetings and thanks

Responder
servimat1
servimat1
138.835
hace 6 años

Correct, so this is the diagram to use. Regards

Responder
adrian0364
hace 6 años

Regards

Responder
adrian0364
hace 6 años

Ask the transformer comes apart or the contactor also acts as a transformer

Responder
adrian0364
hace 6 años

Sorry the last question if I put a thermal relay how would the connection of the diagram that you passed me from already thank you very much

Responder
servimat1
servimat1
138.835
hace 6 años

The transformer is a separate or separate device. As for the thermal relay, you connect it to the output of the contactor without more or the NC contacts are connected in series with the supply of the contactor.

Responder
adrian0364
hace 6 años

Great thank you very much sorry for the questions

Responder
servimat1
servimat1
138.835
hace 6 años

There is no problem that you consult any questions you have. We are for that.

Responder
adrian0364
hace 6 años

Thanks greetings

Responder
adrian0364
hace 6 años

I have a problem the contactor that I have does not have the A1 and A2 located in the same position as the diagram and I do not get to see the numbers below the contactor to see if they are the same it could be that the numbers or the position of the cables vary From already thank you very much

Responder
servimat1
servimat1
138.835
hace 6 años

What brand and model is the contactor? A1 and A2 are always from its coil, the one that is usually repeated in its connection is A2. Upload a photo of the device to indicate.

Responder
adrian0364
hace 6 años

Sorry for the delay but my cell had broken. The brand is general electric

Responder
adrian0364
hace 6 años

The model is cl00A310t6
I can't upload photos I don't know how to forgive

Responder
adrian0364
hace 6 años

Sorry for the trouble if you could help me it would help me a lot I need to finish this thanks

Responder
servimat1
servimat1
138.835
hace 6 años

Usually the coil of the contactors is of another color. There you will find an A1 and two A2 Is that your doubt?

Responder
adrian0364
hace 6 años

No, I doubt that I eat. A1 and A2 of my contactor are in a different position than the diagram you sent me if the ones below 2 or 4 and 6 can also change position because in the diagram that you passed me I can't see the numbers from already thank you very much

Responder
servimat1
servimat1
138.835
hace 6 años

Can you upload a photo of the contactor? Everyone I know comes with its coil indicating the operating voltage and its connection terminals (A1 and A2)

Responder
adrian0364
hace 6 años

He doesn't let me upload the picture I don't know what to do 2t1 contacts. 4t2. 6t3 are the same as in the photo I have them in that order from left to right at the bottom is the same as in the photo because I can't see them

Responder
servimat1
servimat1
138.835
hace 6 años

Those are power terminals. Those of the coil are always A1 and A2.

Responder
adrian0364
hace 6 años

Ok, what I want to know is if they are the same in all contactors or they vary the position depending on the mark on 2t1.the 4t2.and the 6t3 so I copy the plane you passed me to be able to connect everything

Responder
adrian0364
hace 6 años

And if you have a diagram with thermal relay better

Responder
servimat1
servimat1
138.835
hace 6 años

All contactors have the same nomenclatures. As for the thermal relay, it is connected to the output of the contactor and if you want it to cut as a protection you have to use it in series with the contactor coil.

Responder
adrian0364
hace 6 años

Yes, but they have the same position as mine because in the diagram you passed me it is not clear from 2 to 4 and 6

Responder
adrian0364
hace 6 años
hace 6 años
And as for the thermal relay as I connect it in series
servimat1
servimat1
138.835
hace 6 años

The thermal relay goes to the output of the contactor. They have a pair of auxiliary contacts. You must use the NC to connect the contactor coil.

Responder
adrian0364
hace 6 años

OK thank you very much

Responder
Reparaciones similares solucionadas

¿Conoces una solución?

¡Aprende a reparar con estos cursos YoReparo!

4.25
(8)

Reparación de Placa Main TV LED con el Ing. Picerno

Ing. Alberto H. Picerno
$ 40 USD
$ 20 USD
4.94
(16)

Curso Refrigeración Comercial Aplicado a Diagnóstico y Reparación

Ing. Georga Melgarejo
$ 40 USD
$ 13 USD
4.71
(7)

Curso TV OLED y QLED con el Ing. Picerno

Ing. Alberto H. Picerno
$ 29 USD
$ 10 USD
¿Tienes una mejor respuesta a este tema? ¿Quieres hacerle una pregunta a nuestra comunidad y sus expertos?
Regístrate gratis