Household Electricity

Add Outlet between 2 other Sockets

ale082000
hace 5 años
hace 5 años
Hello everyone; I want to check the following, I have to connect an outlet and I want to know if any of the 2 ways are good, or technically there are differences in the way of connecting the socket 2 with the cables that bring the current. The socket that I want to add (called socket 2) is in the middle of other sockets that obtain current from a box that brings the "main" cables from a thermal, and they are spliced to the socket 1 and socket 3, and I don't know if splice from that box to put the socket 2 (as I did with the other sockets) or I can splice it from the cables that connect the junction box with the socket 3 and go through the box where the socket 2 would go. I put a scheme to improve the idea. Regards and thank you all. [url = / ver-adjunto / aHR0cHM6Ly9jZG4ueW9yZXBhcm8uY29tL3VwbG9hZHMvZGVmYXVsdC8wMDAyLzIxL1RvbWFzLTcwODMxLkpQRw / pj / img.ng/g.ng/g.ng/g.ng/g.ng/g.png/g/png/g/png/png/png/png/wp/png/wp.png/wp.png/wp.png # #
ratonelect63
ratonelect63
5.308
hace 5 años

if you can do the 2 better but both ok

Responder
Dr. electron
hace 5 años
hace 5 años
The connection is fine. But you have to keep in mind what use you will give to the additional shot. Taking care not to exceed the current capacity of the connection. I guess what you call thermal is an electromagnetic switch (breaker)
elektomaq
elektomaq
62.202
hace 5 años
hace 5 años
It will always be better from the distribution box, but it does not mean that if it is closer from an outlet you cannot do it from there What you cannot do is connect the socket 2 directly to the socket 3 but if you can connect it to the cable of the socket 3 minimum section of all conductors 2.50 mm² the load of each of these compromised sockets and the circuit that feeds it must also be evaluated comment
javiero
javiero
10
hace 5 años
hace 5 años
Hello, under the thermo-magnetic you have to go out with a single circuit, and you connect each outlet A single circuit is safe, if it is well designed and built, for the loads you need, the more simple and tidy your installation is, the easier it will be to modify it, or find faults in the future. Success Regards
ale082000
hace 5 años
hace 5 años
Thanks to all for their contributions, that shot will not have much load, just a music consolita with its power of 100w, which will never be used to full, and is provisional these days, the shot 3 uses a portable air that gives I consume about 5 amperes (I measured it with the amperometric clamp) the air accuses capacity and cooling 3500w, and consumption of (I think) cooling 1450w .. so the clamp should mark me something like 7 amperes right? but it marked me 5. In shot 1 there will be 2 pc of home use (no games or large source consumption for the graphics) In a short time, the cables will be changed tending to new total, and there I will put the cables from the sectional board thermal I will take out the temporary thermal that I have now in that piece) and all the cables for the shots I will join them to that main line that comes from the thermal sectional for shots as it should be. Greetings and thanks to all for your help.
elektomaq
elektomaq
62.202
hace 5 años

Okay
The 1450W air must be maximum cooling capacity. Real capacity is always something less

Responder
Reparaciones similares solucionadas

¿Conoces una solución?

¡Aprende a reparar con estos cursos YoReparo!

4.25
(8)

Reparación de Placa Main TV LED con el Ing. Picerno

Ing. Alberto H. Picerno
$ 40 USD
$ 20 USD
4.71
(7)

Curso TV OLED y QLED con el Ing. Picerno

Ing. Alberto H. Picerno
$ 29 USD
$ 10 USD
4.64
(11)

Curso Electrónica para Reparación de Placas

Santiago Cediel
$ 29 USD
$ 11 USD
¿Tienes una mejor respuesta a este tema? ¿Quieres hacerle una pregunta a nuestra comunidad y sus expertos?
Regístrate gratis