Hi everyone, My problem is the following, on my electrical board I have no place to add more thermal. I have capacity for 8 modules, one for circuit breaker, 5 sections of the house + 3 outputs for air conditioners. This gives me 9 modules, so I don't get the thermal ones. The solutions can be to gather some sections of the house, or to join sections of AC. My question is: if you sent to each AC with 2.5 wires and all together in a thermal of 20A or 25 A. Can I have problems? The cables are independent from each AC outlet to the box where they would join in the thermal. Thank you for your answers.
elektomaq
elektomaq
62.202
hace 5 años

Where are you writing us from

Responder
chinito
hace 5 años

From Buenos Aires

Responder
servimat1
servimat1
138.835
hace 5 años
hace 5 años
Hi. If you want to place more thermal but you have no place, what you can do is add a small cabinet by air next to its electrical connection or one outside for all AA. regards
chinito
hace 5 años

The idea is in the future to stuff another box up. This is provisional.
regards

Responder
elektomaq
elektomaq
62.202
hace 5 años

Do not think about provisional assumptions, these "provisional" things end up lasting years

Responder
elektomaq
elektomaq
62.202
hace 5 años
hace 5 años
The differential occupies 2 modules 5 sections of the house should occupy 10 modules 3 air conditioners should occupy 6 modules total 18 modules plus 20% free total 22 modules that would be the number of modules that it requires if you use unipolar thermal which are prohibited would occupy 10 modules What is recommended to do in your case is to incorporate to the side an external cabinet (If you can not stuff it) of 12 modules and change the unipolar thermal by bipolar. If you do not agree with this measure, and you only want to reduce the place, the maximum thermal to be used for the three Aires is 20A, there would be no problem in placing three Aires in the same circuit but it is possible that with 20A it will not reach ( That depends on the capacity of the equipment) Cheers

¿Conoces una solución?

¡Aprende a reparar con estos cursos YoReparo!

4.25
(8)

Reparación de Placa Main TV LED con el Ing. Picerno

Ing. Alberto H. Picerno
$ 40 USD
$ 20 USD
4.73
(22)

Curso Reparación de Fuentes Conmutadas de PC y Equipos Electrónicos

Maximiliano Resch
$ 40 USD
$ 20 USD
4.87
(15)

Curso Diseño de Amplificadores de Máxima Fidelidad

Maximiliano Resch
$ 29 USD
$ 13 USD
¿Tienes una mejor respuesta a este tema? ¿Quieres hacerle una pregunta a nuestra comunidad y sus expertos?
Regístrate gratis