Water Heaters (Calefones)

Low boiler pressure

Daniel Borrego
hace 5 años
hace 5 años
I can not raise the pressure in mini duo boilers I have placed 12 units in a building and the maximum that arrive is 0.800 or 1 kilo of pressure depending on the floor there are no losses the radiators are purged I put a pressurizing pump and the pressure does not reach 1,500 who asks for the boiler most starts then stops and throws error 1 I do not know what to do but the technicians of the warranty do not take care of why they say there is air or leaks in the radiators but in the 12 similar I am a plumber from 20 years ago years please some solution thank you
Calemdq
Calemdq
23.097
hace 5 años
hace 5 años
Hi with 0.8 bar they have to walk without problems, if you want more pressure you will have to place a pressurizer at the exit of the general tank; surely in the higher floors is where you have more problems, did you do the hydraulic tests on the circuits of each apartment? Comment and see how to continue, greetings!
Daniel Borrego
hace 5 años

Look at the departments with less pressure are the highest I put a lunftof pressurizing pump in the boiler water inlet and the pressure reaches 0.5 bar the boiler starts resetting it but when it cools it throws error1 the whole circuit is tested at 4kilos my question is there is no way to give the pressure 1.5 that the manufacturer asks either manually or some regulator why the departments are already occupied and people are driving me crazy and I can't find the solution Peisa technicians wash their hands any idea thanks

Responder
Calemdq
Calemdq
23.097
hace 5 años

Do you have a pressure gauge to check the boilers? As if to begin to have real data of the boiler inlet pressure, on the other hand it would be necessary to see if the boiler expansion vessels are with the correct dry side pressure, in the auto wheel valve check the pressure that has, must be 1 kilo. Unfortunately they put the worst mark with technicians according to it

Responder
Daniel Borrego
hace 5 años

Look supposedly the pump pulls 10 bars should be enough about the expansion vessel I do not know the boilers are new but were collected for at least 2 years the pressure of the vessel can give low pressure they told me that the pressure of the start why some with 0.50 work now thanks for answering my questions

Responder
Calemdq
Calemdq
23.097
hace 5 años

I miss a lot, because with 0.7 kilo the Peisa walk without problem, so you have to do a dynamic test, that is, connect a pressure gauge on the return to see what really happens when you load it, make it heat half an hour to the maximum and cut to see what happens as it cools, but we are talking about what we do not know, start at least this test, observe that it accuses the pressure gauge as it heats and once the burner cuts, then comment that you observed and there I can tell you which side to grab. regards !

Responder
Daniel Borrego
hace 5 años

The manometer on the return would be at the outlet of the domestic hot water the manometer that I have is for measuring air I do not know if it is used to measure water

Responder
Daniel Borrego
hace 5 años

Another question the pressure of 1.5 that they ask for the boiler does not arrive because of the height of the tank or because of another problem the tank is 16 meters high is 10,000 liters the building is three stories and ground floor the pipes are 3/4 thermofusion with reduction A1 / 2 in the toilets. We are building another one that boilers have less problems to advise me since the Peisa never thanks again

Responder
Calemdq
Calemdq
23.097
hace 5 años

The pressure gauges are used to measure pressures of liquids or gases; the pressure must be measured on the return just where the return is connected to the boiler, place a t and connect it there

Responder
Calemdq
Calemdq
23.097
hace 5 años

If you want to avoid problems, in future installations, for example, if an orbis is mid-range and if a Baxi is mid-range, they are more reliable and have guaranteed technical service,

Responder
Daniel Borrego
hace 5 años

I tell you that a Peisa technician will come in the week I hope he gives me a solution I don't know what else to do then I tell them

Responder
Daniel Borrego
hace 5 años
hace 5 años
Finally the peisa technician came the only solution he gave me is to put a pressurizing pump at the entrance of the boiler to purge the entire circuit controlling the air in the expansion vessel. The pressure never reached the one requested by the manufacturer. He charged me 950 Weights and went the next day I throw error 1. I solved it with an automatic trap that has the recirculating pump but it comes with a tight conical plug, loosen it, it came out, the air was cleared, the error was cleared and holy remedy
Calemdq
Calemdq
23.097
hace 5 años

That is, it had air in the circuit; the problem of the air in the pipe is that the air is elastic, it compresses and expands the pressure or temperature depends and the actual pressure reading is wrong, so I insist so much with the purging

Responder
Reparaciones similares solucionadas

¿Conoces una solución?

¡Aprende a reparar con estos cursos YoReparo!

4.25
(8)

Reparación de Placa Main TV LED con el Ing. Picerno

Ing. Alberto H. Picerno
$ 40 USD
$ 20 USD
4.87
(15)

Curso Diseño de Amplificadores de Máxima Fidelidad

Maximiliano Resch
$ 29 USD
$ 13 USD
4.64
(45)

Curso Tecnología Inverter - Fabricación de probadores y herramientas

Yamil Alarcón
$ 240 USD
$ 40 USD
¿Tienes una mejor respuesta a este tema? ¿Quieres hacerle una pregunta a nuestra comunidad y sus expertos?
Regístrate gratis