Water Heaters (Calefones)

My caldera peisa goes out

FEMAGA
FEMAGA
2
hace 6 años
hace 6 años
Hello!!! I have a hot water heating circuit with radiators. The problem that occurs to me is that I have to put the boiler to the maximum so that it lasts longer, because if I put it in a lower level of heating, it starts to lose pressure and ends up going out. Call Peisa people came to look at her and told me that I have some loss somewhere and this causes me to lose pressure. Adjust all radiators and none lose. The pipes that go from one radiator to another are thermofusion and I do not see anything on the wall that makes me think of a loss. The walls are not damp. These people have already come several times and do not find the solution and the worst thing is that they charge the visit. I would appreciate if you could give me a hand. Thank you very much
Calemdq
Calemdq
23.097
hace 6 años

What error does it give you when it goes out?

Responder
FEMAGA
FEMAGA
2
hace 6 años

Put E1. That would be lack of water pressure

Responder
WGinstalaciones
hace 6 años
hace 6 años
Hi, I got someone to do a circuit proofing. So you rule it out as a leak and focus on the boiler.
Calemdq
Calemdq
23.097
hace 6 años
hace 6 años
Hello Although the E1 announces the lack of pressure in the circuit, what can be happening is that when put at maximum power the water boils and that steam is vented by the air trap of the boiler and there the pressure is lost; as a first step, two tests must be carried out: one for watertightness and one for water circulation; since if the flow of water does not move with fluidity also happens that. Did Peisa's people check the pump if it works correctly? Regards !
FEMAGA
FEMAGA
2
hace 6 años

Hello.!!! She is afraid that I have to put at maximum so it lasts longer the boiler. If you turn it on less, it turns off faster. Peisa people tell me that there must be a leak somewhere but I do not understand why the boiler is turned off. They tell me the boiler is good.

Responder
Calemdq
Calemdq
23.097
hace 6 años

To know if the boiler is going well, you have to do the tests that I told you, but it is impossible to diagnose a fault

Responder
FEMAGA
FEMAGA
2
hace 6 años

You have someone to recommend. I'm from the south. Adrogue. Thank you

Responder
Cune
hace 6 años
hace 6 años
Hi: to discard that it is the boiler you can disconnect the heating and bridge it with a flexible. If this works well you have to focus on finding the lost. If you get a thermographic camera would be ideal.
Reparaciones similares solucionadas

¿Conoces una solución?

¡Aprende a reparar con estos cursos YoReparo!

4.84
(25)

Curso Práctico de Reparación y Bobinado de Motores Eléctricos

Héctor Castiñeira
$ 60 USD
$ 20 USD
4.73
(22)

Curso Reparación de Fuentes Conmutadas de PC y Equipos Electrónicos

Maximiliano Resch
$ 40 USD
$ 20 USD
4.64
(45)

Curso Tecnología Inverter - Fabricación de probadores y herramientas

Yamil Alarcón
$ 240 USD
$ 40 USD
¿Tienes una mejor respuesta a este tema? ¿Quieres hacerle una pregunta a nuestra comunidad y sus expertos?
Regístrate gratis